SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03911
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/23/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL FIRE PROTECTION INSPECTION OF THIS PROPERTY THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS 1) THE FIRE DEPARTMENT CONNECTION BY THE SHOWROOM SHALL BE VISABLE AND ACCESSABLE. VEGETATION SHALL BE REMOVED WITH IN 3 FEET OF THE APPLIANCE 2) IN THE DETAIL AREA ALL ITEMS SHALL BE REMOVED FROM SPRINKLER PIPING. ( AIR AND GARDEN HOSES) 3) TWO (2) CHROME VIKING 1/2 INCH HORIZONTAL SIDEWALL SPRINKLER HEADS SHALL BE PROVIDED THE SPARE HEAD BOX 4) THE WATER MOTOR GONG DID NOT FUNCTION AND SHALL BE REPAIRED. 5) SHOP AREA-CHECK LIGHTS THAT ARE MOUNTED TO 4' WIDE PANELS AT THE TOP OF THE BOWSTRING ROOF. IF NECESSARY, RELOCATE LIGHTS.