Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/22/2008

Applicant:

PARK MALL LLC

Description:

Aldo #126, initial inspection conducted 10/20/08

Outstanding Inspections

Case Number: T08FR03896
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/22/2008 VIOL - ADMINISTRATION DGREENLE Correction Required SECTION 107, MAINTENANCE TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device... or any other feature is required for compliance with the provisions of this code, or otherwise installed, (it) shall thereafter be continuously maintained. _____ Repair emergency light, stock room.
10/22/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
10/22/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Adjust sprinkler head in bathroom and replace escutcheon. Do not let storage above bathroom lean against sprinkler piping and components.
10/22/2008 VIOL - MEANS OF EGRESS DGREENLE Correction Required Blocked exit: TFC 1003.6 - Means of egress continuity. Obstructions shall not be placed in the required width of a means of egress. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03896
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
10/22/2008 INSP - FULL DGREENLE Approved Extinguishers Serviced and Tagged (02/08) - Occupant shall perform monthly inspections and indicate such on tag. Remember to keep extinguishers unobscured and unobstructed.
10/22/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy: NOT CURRENT - Occupant shall obtain a current C of O. Occupancy Class/Hazard Level have NOT changed.
12/17/2008 INSP - REINSPECTION DGREENLE Approved -- APPROVED