Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/16/2008

Applicant:

PARK MALL LLC

Description:

Inittial inspection Brighton Collectables

Outstanding Inspections

Case Number: T08FR03793
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
10/16/2008 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.
10/16/2008 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03793
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/16/2008 INSP - FULL JLOYA Approved C of O on file Extinguishers up to date
11/03/2008 COMPL - REINSPECTION DGREENLE Approved