Case: T08FR03793
Case Details
Entered Date:
10/16/2008
Applicant:
PARK MALL LLC
Description:
Inittial inspection Brighton Collectables
Outstanding Inspections
Case Number: T08FR03793
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2008 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |
10/16/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03793
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2008 | INSP - FULL | JLOYA | Approved | C of O on file Extinguishers up to date |
11/03/2008 | COMPL - REINSPECTION | DGREENLE | Approved |