Applicant:

PARK MALL LLC

Description:

GAP #116 & #118, full inspection conducted 10/13/08

Outstanding Inspections

Case Number: T08FR03733
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/13/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Extension Cords: TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. _____ Break room, snack machine.
10/13/2008 VIOL - FIRE RESIST.RATED CONST DGREENLE Violation Opening protectives TFC 703.2 - Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fire door assemblies shall not be modified. _____ Do not prop fire doors open.
10/13/2008 VIOL - MEANS OF EGRESS DGREENLE Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
10/13/2008 VIOL - MEANS OF EGRESS DGREENLE Violation MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03733
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/13/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy: ON FILE
11/17/2008 INSP - REINSPECTION DGREENLE Approved