Case: T08FR03731
Case Details
Entered Date:
10/13/2008
Applicant:
PARK MALL LLC
Description:
Guess #124, full inpsection conducted 10/13/08
Outstanding Inspections
Case Number: T08FR03731
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2008 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Violation | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ stock room shelving |
10/13/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit sign, back of sales floor, west exit. |
10/13/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | Blocked exit: TFC 1003.6 - Means of egress continuity. Obstructions shall not be placed in the required width of a means of egress. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03731
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy on file Extinguishers serviced and tagged (occupant shall provide monthly inspections and indicate such on tag) |