Description:

sprinkler test needed

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03532
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
12/02/2008 VIOL - MEANS OF EGRESS BCORRALE Approved 1011.2- Exit sign out of service. ___Repair sign.
12/02/2008 VIOL - MEANS OF EGRESS BCORRALE Approved 1008.1.8.3- Main entrance needs sign stating: THIS DOOR SHALL REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. ___Install sign.
12/02/2008 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Approved 901.6- Sprinkler system due for annual test. __Have system tested.
12/02/2008 VIOL - FIRE RESIST.RATED CONST BCORRALE Approved 703.1- Ceiling vent, tile missing. ___Replace tile.
12/02/2008 VIOL - FIRE SERVICE FEATURES BCORRALE Approved 510.1-Sprinkler riser room door not labeled. ___Label door.
12/02/2008 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved 315.2.3- Sprinkler room has combustible storage. ___Remove storage.
12/02/2008 INSP - FULL BCORRALE Approved Full inspection on 10/30/08.