Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03527
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
10/03/2008 INSP - FULL RSPANGLE Approved 5.) TFC 901.6.2 THE SPRINKLER SYSTEM IS PAST DUE FOR ANNUAL INSPECTION. HAVE SYSTEM INSPECTED AND CORRECT ANY NOTED DEFICIENCIES.
10/03/2008 INSP - FULL RSPANGLE Approved 4.) TFC 1011.5.3 CHECK ALL INTERNALLY ILLUMINATED EXIT SIGNS TO ENSURE THEY ARE FUNCTIONING PROPERLY. REPAIR/REPLACE MALFUNCTIONING UNITS.
10/03/2008 INSP - FULL RSPANGLE Approved 3.) TFC 703.1.1 REPLACE THE CEILING TILE IN THE HALLWAY OUTSIDE OF THE KITCHEN TO PROVIDE REQUIRED FIRE BLOCKING AND DRAFT STOPPING.
10/03/2008 INSP - FULL RSPANGLE Approved 2.) TFC 605.6 THE ELECTRICAL JUNCTION BOX IN THE DRY STORAGE ROOM NEEDS A COVER PLATE INSTALLED.
10/03/2008 INSP - FULL RSPANGLE Approved 1.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT IN THE BELLASTANZA ROOM IS NOT WORKING. CHECK ALL EMERGENCY ILLUMINATION UNITS THROUGHOUT THE FACILITY AND VERIFY THAT THEY OPERATING. REPAIR /REPLACE INOPERABLE UNITS.