Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/02/2008

Applicant:

BUILDER S FASHION SQUARE LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03510
Case Description: INSPECTION
Total Completed Inspections - 19
End Date Description Inspector Results Comments
10/02/2008 INSP - FULL RSPANGLE Approved 19.) TFC 901.6.2 THE BUILDING'S SPRINKLER SYSTEM MUST HAVE AN ANNUAL, FULL SYSTEM, INSPECTION AND A 5 YEAR CHECK VALVE INSPECTION IS REQUIRED.
10/02/2008 INSP - FULL RSPANGLE Approved 18.) TFC 2301.3 LOWER THE STORAGE ON WAREHOUSE RACKS TO A MAXIMUM OF 12' AND REMOVE SOLID WOOD PANELS FOR THE TOP RACK.
10/02/2008 INSP - FULL RSPANGLE Approved 17.) TFC 605.6 THE ELECTRICAL JUNCTION BOX ON THE WEST WALL OF THE PAD WAREHOUSE MUST HAVE A COVER PLATE INSTALLED.
10/02/2008 INSP - FULL RSPANGLE Approved 16.) TFC 605.3 A 30" WORKING SPACE SHALL BE PROVIDED IN FRONT OF THE ELECTRICAL BREAKER PANEL LOCATED NEAR THE ENTRANCE TO THE WEST WING.
10/02/2008 INSP - FULL RSPANGLE Approved 15.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER BY THE FAR WEST EXIT DOOR OF THE WEST WING MUST BE MOUNTED BACK ON THE WALL.
10/02/2008 INSP - FULL RSPANGLE Approved 14.) TFC 605.6 THE OUTLET IN THE COMMERCIAL OFFICE MUST HAVE A COVER PLATE INSTALLED.
10/02/2008 INSP - FULL RSPANGLE Approved 13.) TFC 3003.5.3 THE HELIUM BOTTLE NEAR THE ENTRANCE TO THE WEST WING MUST BE SECURED TO PREVENT FALLING.
10/02/2008 INSP - FULL RSPANGLE Approved 12.) TFC 1028.2 THE DOUBLE DOORS ON THE NORTH SIDE OF THE PAD WAREHOUSE MUST HAVE "THIS DOOR BLOCKED" SIGN IN ACCORDANCE WITH THE FIRE MARSHAL'S EXITING POLICY.
10/02/2008 INSP - FULL RSPANGLE Approved 11.) TFC THE ELECTRICAL JUNCTION BOX NEAR THE CEILING IN THE NORTHWEST CORNER OF THE WEST WAREHOUSE BY THE HEATING UNIT MUST HAVE A COVER PLATE INSTALLED.
10/02/2008 INSP - FULL RSPANGLE Approved 10.) TFC 605.6 THE ELECTRICAL JUNCTION BOX AT THE BASE OF THE YELOW SUPPORT POST IN THE MDDLE OF THE SOUTH END OF THE WEST WAREHOUSE MUST HAVE A COVER PLATE INSTALLED.
10/02/2008 INSP - FULL RSPANGLE Approved 9.) TFC 605.6 THE ELECTRICAL JUNCTION BOX ON THE FAR WEST WALL OF THE WEST WAREHOUSE BY THE DOUBLE DOORS MUST HAVE A COVER PLATE INSTALLED.
10/02/2008 INSP - FULL RSPANGLE Approved 8.0 TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT OVER THE FAR WEST DOUBLE DOORS NEEDS TO BE REPLACED WITH AN APPROVED UNIT IN THE WEST WAREHOUSE.
10/02/2008 INSP - FULL RSPANGLE Approved 7.) TFC 1028.2 THE FAR WEST DOUBLE DOORS OF THE WEST WAREHOUSE MUST BE SIGNED ON THE OUTSIDE "THIS DOOR BLOCKED" IN ACCORDANCE WITH FIRE MARSHAL'S EXITING POLCIY.
10/02/2008 INSP - FULL RSPANGLE Approved 6.) TFC 605.6 NUMEROUS FLOURESCENT LIGHTS IN THE WEST WAREHOUSE MUST HAVE COVER PLATES IN PLACE TO COVER WIRE SPLICES.
10/02/2008 INSP - FULL RSPANGLE Approved 5.) TFC 605.6 THE ELECTRICAL JUNCTION BOX NEAR THE CEILING BY THE WAREHOUSE OFFICE MUST HAVE A COVER PLATE INSTALLED.
10/02/2008 INSP - FULL RSPANGLE Approved 4.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER BY THE BACK DOOR OF THE WEST WAREHOUSE IS PAST DUE FOR ITS ANNUAL INSPECTION.
10/02/2008 INSP - FULL RSPANGLE Approved 3.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER IN THE WAREHOUSE OFFICE IS PAST DUE FOR ITS ANNUAL INSPECTION.
10/02/2008 INSP - FULL RSPANGLE Approved 2.) TFC 605.6 THE ELECTRIC FAN IN THE OFFICE IS NOT PERMITTED TO BE USED WITH A SPLICE IN THE POWER CORD.
10/02/2008 INSP - FULL RSPANGLE Approved 1.) TFC 1011.4 ALL THE INTERNALLY ILLUMINATED EXIT SIGNS MUST BE ILLUMINATED AT ALL TIMES. REPAIR OR REPLACE EXIT SIGNS.