Case: T08FR03389
Case Details
Entered Date:
10/01/2008
Applicant:
PARK MALL LLC
Description:
Full inspection conducted 9/30/08
Outstanding Inspections
Case Number: T08FR03389
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2008 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Violation | TFC 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures. |
10/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
10/01/2008 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Violation | Opening protectives TFC 703.2 - Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fire door assemblies shall not be modified. _____ Do not prop fire doors open. |
10/01/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | Blocked exit: TFC 1003.6 - Means of egress continuity. ... The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Keep rear exit hallway passable (32") even during stocking |
10/01/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03389
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: NOT CURRENT - Occupant shall obtain a current C of O. Occupancy Class/Hazard Level have NOT changed. Extinguishers Serviced and Tagged (08/08) - Occupant shall perform monthly inspections and indicate such on tag. Remember to keep extinguishers unobscured and unobstructed. |
11/18/2008 | INSP - REINSPECTION | DGREENLE | Approved |