Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

10/01/2008

Applicant:

PARK MALL LLC

Description:

Full inspection conducted 9/30/08

Outstanding Inspections

Case Number: T08FR03389
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
10/01/2008 VIOL - PRECAUTION AGAINST FIRE DGREENLE Violation TFC 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures.
10/01/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
10/01/2008 VIOL - FIRE RESIST.RATED CONST DGREENLE Violation Opening protectives TFC 703.2 - Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fire door assemblies shall not be modified. _____ Do not prop fire doors open.
10/01/2008 VIOL - MEANS OF EGRESS DGREENLE Violation Blocked exit: TFC 1003.6 - Means of egress continuity. ... The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Keep rear exit hallway passable (32") even during stocking
10/01/2008 VIOL - MEANS OF EGRESS DGREENLE Violation MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03389
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/01/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy: NOT CURRENT - Occupant shall obtain a current C of O. Occupancy Class/Hazard Level have NOT changed. Extinguishers Serviced and Tagged (08/08) - Occupant shall perform monthly inspections and indicate such on tag. Remember to keep extinguishers unobscured and unobstructed.
11/18/2008 INSP - REINSPECTION DGREENLE Approved