Case: T08FR03384
Case Details
Entered Date:
10/01/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection conducted 9/30/08
Outstanding Inspections
Case Number: T08FR03384
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
10/01/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03384
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: NOT CURRENT - Occupant shall obtain a current C of O. Occupancy Class/Hazard Level have NOT changed. Extinguishers Serviced and Tagged (10/07) SERVICE DUE SOON Occupant shall perform monthly inspections and indicate such on tag. Remember to keep extinguishers unobscured and unobstructed. |
11/18/2008 | INSP - REINSPECTION | DGREENLE | Approved | Service on emergency light due 11/19 -- RI 11/20 |