Description:

Full Fire Prevention Inspection Building Rep: Veronica Berdgo Phone # 798-3738

Outstanding Inspections

Case Number: T08FR03237
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
09/29/2008 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
09/29/2008 VIOL - PRECAUTION AGAINST FIRE JLONGO Correction Required 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. _____ Remove the combustible material away from the gas water heater.
09/29/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door. 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Fix, repair, and/or replace all exit signs in order to meet code standards ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ____________________ Passed on: ________ (Joseph P. Longo)