Case: T08FR03235
Case Details
Entered Date:
09/29/2008
Applicant:
ST MARYS VILLAGE LLC
Description:
Full Fire Prevention Inspection Building Rep: Murrieta Phone # 520-791-3715
Outstanding Inspections
Case Number: T08FR03235
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2008 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
09/29/2008 | VIOL - FIRE SERVICE FEATURES | JLONGO | Correction Required | 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____ Place the words "THIS DOOR BLOCKED" on the north east door where the beverage fridge us blocking entry. |
09/29/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.4 Multi-plug adapters Multi-plug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC electrical code shall be prohibited. _____ All Multi-plug adapters shall be removed and/or replace with approved fused power strips. |
09/29/2008 | VIOL - FIRE RESIST.RATED CONST | JLONGO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile. The ceiling tile is bowing and will allow the passage of heat and fire. |
09/29/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective _____ Properly align your hood system nozzles with the burners _____ Service and tag all portable fire extinguishers in order to meet code standards 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. _____ Remove all obstructions away from the sprinkler heads and remove any items attached to the sprinkler heads. (pinatas) |
09/29/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door. 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. ______ Remove or disable one of the locking devices from the rear egress door to comply with the fire code. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. |