Case: T08FR03199
Case Details
Entered Date:
09/26/2008
Applicant:
DOREY FAMILY TRUST
Description:
Full Inspection for SIP referral conducted on 9/25/08
Outstanding Inspections
Case Number: T08FR03199
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | ELECTRICAL EQUIPMENT, WIRING AND HAZARDS TFC 605.5 - ...flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. _____ Labor Ready sign/clock |
| 09/26/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | Portable Fire Extinguishers TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
| 09/26/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03199
Case Description: INSPECTION
Total Completed Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2008 | INSP - FULL | DGREENLE | Approved | Upon mitigation of Code violoations noted below, Occupant shall be refered to Self-Inspection Program |
| 09/26/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: C of O is not current. New occupant does not pose different use/hazard level. Occupant shall obtain an updated C of O. |
| 12/04/2008 | INSP - REINSPECTION | DGREENLE | Approved | approved, referred to SIP |