Description:

Full Fire Prevention Inspection.

Outstanding Inspections

Case Number: T08FR02997
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
09/22/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 504.2 Maintenance of exterior doors and openings. 1.Post the wording, "THIS DOOR BLOCKED" on the outside of the egress door located in John's office. NOTE:The wording shall be at least 6 inches high on a contrasting background.
09/22/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, Testing and Maintenance. 1.Service and tag all portable fire extinguishers. 2.Provide documentation of the last sprinkler inspection report and correct any defficenies noted on the report. Service date for the sprinkler system was 11/07.
09/22/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Unlatching. 1.Remove the thumb-turn lock from the east exit door. NOTE:Only one lock is permitted on the exit door.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02997
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/09/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations ahve been corrected.