Case: T08FR02851
Case Details
Entered Date:
09/18/2008
Applicant:
BCT PROPERTIES
Description:
sprinkler report
Outstanding Inspections
Case Number: T08FR02851
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2008 | INSP - FULL | NSPRENGE | Violation | 1) IFC 906.2 General requirements. Portable fire extinguishers shall be maintained in accordance with this section and NFPA 10. A) You will have your fire extinguishers tested and tagged ( 1 noted in showroom storage area). |
11/06/2008 | INSP - FULL | NSPRENGE | Violation | 2) IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. A) You will restrain your cylinders from falling. ( helium tank in closet). |
11/06/2008 | INSP - FULL | NSPRENGE | Violation | 3) IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. A) You will provide access to your electrical panel in closet. B) In Wherehouse ground level near East roll up doors. |
11/06/2008 | INSP - FULL | NSPRENGE | Violation | 4) IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. A) You will cause your emergency lighting to illuminate ( in upstairs 'Click Advertising' recpetion area and stairway. B) In upstairs storage over wherehouse. C) On exit sign over Parts customer waiting area. |
11/06/2008 | INSP - FULL | NSPRENGE | Violation | 5) IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. A) You will provide a faceplate for your electrical outlet in your Mazda file room near rolling file storage. |
11/06/2008 | INSP - FULL | NSPRENGE | Violation | 6) IFC 1028.4 Exit signs. Exit signs shall maintained in accordance with Section 1011 of the 2006 IFC. A). You will cause your exit sign near the parts counter to light. |