Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/16/2008

Applicant:

REAYS' RANCH INVESTORS LLC

Description:

UST Inspection

Outstanding Inspections

Case Number: T08FR02833
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
09/16/2008 INSP - UST BCORRALE Correction Required UST inspection @ Arizona fuel.
09/16/2008 VIOL - MOTOR FUEL DISPENSING BCORRALE Correction Required 2204.2 Attended self-service motor fuel-dispensing facilities. Attended self-service motor fuel-dispensing facilities shall have at least one qualified attendant on duty while the facility is open for business. The attendant's primary function shall be to supervise, observe and control the dispensing of fuel. The attendant shall control sources of ignition, give immediate attention to accidental spills or releases, and be prepared to use fire extinguishers
09/16/2008 VIOL - MOTOR FUEL DISPENSING BCORRALE Correction Required 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times. · Replace all cracked and damaged hoses ( dispenser #2)
09/16/2008 VIOL - MOTOR FUEL DISPENSING BCORRALE Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. · Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
09/16/2008 VIOL - HAZARDOUS MATERIALS,GEN BCORRALE Correction Required 2701.3.3.15 Emergency plan. A written emergency plan shall be developed to ensure that proper actions are taken in the event of an emergency, and the plan shall be followed if an emergency condition occurs. The process of developing and updating the plan shall involve the participation of affected employees. A written emergency plan must be developed and all employees properly how to respond to the emergency. A spill clean up kit must also be available for the containment of small spills (5 gallons or less).
09/16/2008 VIOL - FLAMMABLE LIQUIDS BCORRALE Correction Required 3404.2.12.3 Existing tanks and piping. Existing underground storage tanks and piping shall be tested for leakage at the owner's or operator's expense at least every 24 months in accordance with this section. EXCEPTION: Underground storage tank systems with an approved method of detecting leaks from any component of the system. Tanks shall be emptied of flammable or combustible liquids if required tests are not completed within the specified time. When testing is required, owners or operators shall provide the fire code official with data setting forth the method of testing that is to be used and shall submit the name of a qualified individual who will conduct the test. A testing permit shall be obtained. The method of testing to be used shall consider the effects of temperature, pressure and other variables and shall establish conclusively whether the tank or piping is leaking. Pneumatic testing is prohibited. Devices used for final testing shall be capable of detecting leaks as small as 0.05 gallon per hour. Leaking piping and equipment shall not be used until repaired or replaced. The fire code official is authorized to require that the test be conducted in the code official's presence. · Please provide a copy of either the tank tightness and line leak test results or if a automatic tank gauge system is used please provide the annual calibration test report for that device and the print out showing that the system has passed its leak test.
09/16/2008 VIOL - FLAMMABLE LIQUIDS BCORRALE Correction Required 3404.2.7.10 Leak reporting. A consistent or accidental loss of liquid, or other indication of a leak from a tank system, shall be reported immediately to the fire department, the fire code official and other authorities having jurisdiction. The sump shall be emptied of all fluids properly and all piping inspected for leaks. It is in violation to not report an indication of a leak.