Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/08/2008

Applicant:

TUCSON ST MARY'S PLAZA LLC

Description:

Full Fire Prevention Inspection. Debbie Dorr 622-7447

Outstanding Inspections

Case Number: T08FR02704
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
09/08/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1.Lower the UPS signs located in the sales area to 18 inches below the sprinkler head deflectors or place the signs directly against the wall.
09/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____1.Remove the broken panic hardware from the East egress door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02704
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/22/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.