Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/08/2008

Applicant:

CFT DEVELOPMENTS LLC

Description:

Full Fire Prevention Inspection. Sergio Magallanes 520-622-8699

Outstanding Inspections

Case Number: T08FR02703
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
09/08/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. _____1.Remove the gasoline from the electrical room located by the exit door in the kitchen. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/08/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1.Clean and remove all grease accumulation from the hood system and provide documentation of such work.
09/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system _____1.Repair or replace the emergency lighting unit located on the wall in the kitchen by the soda machine boxes.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02703
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/22/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.