Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR02655
Case Details
Entered Date:
09/05/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection conducted 9/3/08
Outstanding Inspections
Case Number: T08FR02655
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electric transformer and maintain clearance in front of electrical panels. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02655
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE |
10/01/2008 | COMPL - REINSPECTION | DGREENLE | Approved | --- APPROVED 9/30/08 |