Case: T08FR02651
Case Details
Entered Date:
09/05/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection 9/3/08
Outstanding Inspections
Case Number: T08FR02651
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels. |
09/05/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | 1011.2 Illumination. Exit signs shall be internally or externally illuminated. _____ Replace batteries in exit sign over front door _____ Replace/repair exit signs that are bruned/melted |
09/05/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | MEANS OF EGRESS ILLUMINATION TFC - 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Replace batteries in emergency lighting |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02651
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE |
10/01/2008 | COMPL - REINSPECTION | DGREENLE | Approved | --- APPROVED Maintenance Notes: Don't let stock/furnisnings collect around electrical panels Fire doors are not to be propped open Keep exit hallway clear even during stocking |