Applicant:

PARK MALL LLC

Description:

Full Inspection 9/3/08

Outstanding Inspections

Case Number: T08FR02651
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
09/05/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels.
09/05/2008 VIOL - MEANS OF EGRESS DGREENLE Violation 1011.2 Illumination. Exit signs shall be internally or externally illuminated. _____ Replace batteries in exit sign over front door _____ Replace/repair exit signs that are bruned/melted
09/05/2008 VIOL - MEANS OF EGRESS DGREENLE Violation MEANS OF EGRESS ILLUMINATION TFC - 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Replace batteries in emergency lighting

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02651
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
09/05/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy: ON FILE
10/01/2008 COMPL - REINSPECTION DGREENLE Approved --- APPROVED Maintenance Notes: Don't let stock/furnisnings collect around electrical panels Fire doors are not to be propped open Keep exit hallway clear even during stocking