Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR02634
Case Details
Entered Date:
09/04/2008
Applicant:
LCC-BEAR CANYON/TANQUE VERDE LLC
Description:
UST Inspections
Outstanding Inspections
Case Number: T08FR02634
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/04/2008 | INSP - UST | BCORRALE | Correction Required | Inspection of Catalina Mart #13, 9/4. |
09/04/2008 | VIOL - MOTOR FUEL DISPENSING | BCORRALE | Correction Required | 2204.2 Attended self-service motor fuel-dispensing facilities. Attended self-service motor fuel-dispensing facilities shall have at least one qualified attendant on duty while the facility is open for business. The attendant's primary function shall be to supervise, observe and control the dispensing of fuel. The attendant shall control sources of ignition, give immediate attention to accidental spills or releases, and be prepared to use fire extinguishers. |
09/04/2008 | VIOL - MOTOR FUEL DISPENSING | BCORRALE | Correction Required | 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times. · Replace all cracked and damaged hoses · #1 short hose · #2 both hoses · #7 short hose |
09/04/2008 | VIOL - MOTOR FUEL DISPENSING | BCORRALE | Correction Required | 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. · Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer. |
09/04/2008 | VIOL - FLAMMABLE LIQUIDS | BCORRALE | Correction Required | 3404.2.12.3 Existing tanks and piping. Existing underground storage tanks and piping shall be tested for leakage at the owner's or operator's expense at least every 24 months in accordance with this section. EXCEPTION: Underground storage tank systems with an approved method of detecting leaks from any component of the system. Tanks shall be emptied of flammable or combustible liquids if required tests are not completed within the specified time. When testing is required, owners or operators shall provide the fire code official with data setting forth the method of testing that is to be used and shall submit the name of a qualified individual who will conduct the test. A testing permit shall be obtained. The method of testing to be used shall consider the effects of temperature, pressure and other variables and shall establish conclusively whether the tank or piping is leaking. Pneumatic testing is prohibited. Devices used for final testing shall be capable of detecting leaks as small as 0.05 gallon per hour. Leaking piping and equipment shall not be used until repaired or replaced. The fire code official is authorized to require that the test be conducted in the code official's presence. · Please provide a copy of either the tank tightness and line leak test results or if a automatic tank gauge system is used please provide the annual calibration test report for that device and the print out showing that the system has passed its leak test. · Veeder Root is in various states of alarm. |
09/04/2008 | VIOL - FLAMMABLE LIQUIDS | BCORRALE | Correction Required | 3404.2.7.10 Leak reporting. A consistent or accidental loss of liquid, or other indication of a leak from a tank system, shall be reported immediately to the fire department, the fire code official and other authorities having jurisdiction. The sump shall be emptied of all fluids properly and all piping inspected for leaks. It is in violation to not report an indication of a leak. · Center sump contains liquid, needs to be emptied |