Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/04/2008

Applicant:

LDR-SILVERBELL LLC

Description:

Full Fire Prevention Inspection. Jessica Sarmiento 884-0714

Outstanding Inspections

Case Number: T08FR02632
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1.Remove both surface bolts from the egress doors located in the employee's only area.
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 2. The maximum unlatching force shall not exceed 15 pounds (67 N). _____1.Repair the panic hardware located on the rear exit door. NOTE:Too much force is required to activate the hardware and open the door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.The exit sign located above the rear exit door shall have emergency back-up power. _____2.The exit sign located above the entrance/exit door shall have emergency back-up power.
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1.Remove the double-keyed lock from the entrance/exit door.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02632
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/01/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.