Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/04/2008

Applicant:

LDR-SILVERBELL LLC

Description:

Full Fire Prevention Inspection. Jesica Figueroa 882-8047

Outstanding Inspections

Case Number: T08FR02627
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/04/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1.Remove the cube adapter located behind the washer and dryer in the back room. NOTE:Replace the cube adapter with a fused multi-plug adapter.
09/04/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1.The electrical outlet on the East wall located in the display area shall have an approved outlet cover.
09/04/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Service and tag the portable fire extinguisher. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/04/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.The exit sign located above the main entrance/exit door shall have emergency back-up power.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02627
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/01/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.