Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/02/2008

Applicant:

LDR-SILVERBELL LLC

Description:

Full Fire Prevention Inspection. Evan Figueroa 792-2075

Outstanding Inspections

Case Number: T08FR02602
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Provide documentation of the last hood system inspection report.
09/02/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1.Clean and remove all grease accumulation from the kitchen hood system or provide documentation of such work. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/02/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1.Remove the surface bolt from the exit door located in the kitchen.
09/02/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4 Power source. Where emergency illumination is required in Section 1027.5, exit signs shall be visible under emergency illumination conditions. _____1.The exit sign located above the entrance/exit door shall have emergency back-up power.
09/02/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1.Properly secure the compressed gas cylinders located in the kitchen to the wall or fixed object with a chain or strap.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02602
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/03/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.