Case: T08FR02601
Case Details
Entered Date:
09/02/2008
Applicant:
PARK MALL LLC
Description:
Full inspection 8/28/08
Outstanding Inspections
Case Number: T08FR02601
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical transformer and panels. |
09/02/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | Portable Fire Extinguisher TFC 906.6 - Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. TFC 906.7 Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. TFC 906.9 - Portable fire extinguishers having a gross weight not exceeding 40 pounds shall be installed so that its top is not more than 5 feet above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds shall be installed so that its top is not more than 3.5 feet above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches. _____ Mount extinguishers in an approved manner. |
09/02/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | MEANS OF EGRESS ILLUMINATION 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Replace battery in emergency light |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02601
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/02/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE AND POSTED, thank you |