Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/02/2008

Applicant:

PARK MALL LLC

Description:

Full Inspection 8/28/08

Outstanding Inspections

Case Number: T08FR02593
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting for back room. _____ Provide emergency lighting for back exit hallway.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02593
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
09/02/2008 INSP - FULL DGREENLE Approved NOTE: Exit Sign at rear exit is very dim. Consider replacing batery soon.
09/02/2008 INSP - FULL DGREENLE Approved Maintain a clear area around electrical panel and transformer (TFC 605.3 requires 36").
09/02/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy on file
11/18/2008 INSP - REINSPECTION DGREENLE Approved