Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/02/2008

Applicant:

PARK MALL LLC

Description:

Full Inspection 8/28/08

Outstanding Inspections

Case Number: T08FR02590
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/02/2008 INSP - FULL DGREENLE Correction Required 1997 Uniform Administrative Code Section 309.5 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official.
09/02/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels.
09/02/2008 VIOL - MEANS OF EGRESS DGREENLE Violation Illumination required. TFC 1006.1 - The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Replace battery in egress light - back room
09/02/2008 VIOL - MEANS OF EGRESS DGREENLE Violation TFC 1011.2 - Exit signs shall be internally or externally illuminated. _____ back room

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02590
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/01/2008 COMPL - REINSPECTION DGREENLE Approved -- APPROVED 9/30/08