Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/29/2008

Applicant:

PARK MALL LLC

Description:

Full Inspection 8/29/08

Outstanding Inspections

Case Number: T08FR02585
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
08/29/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels and around transformer.
08/29/2008 VIOL - MEANS OF EGRESS DGREENLE Violation Emergency egress lighting 1006.1 The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Replace batteries in emergency lighting units in stock room and test.
09/30/2008 INSP - REINSPECTION DGREENLE Continued NEXT RI 10/15
10/01/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Do not store items against or tie items to or hang items from sprinkler lines (above bathroom)

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02585
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/29/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy: ON FILE
10/20/2008 COMPL - REINSPECTION DGREENLE Approved -- APPROVED