Case: T08FR02584
Case Details
Entered Date:
08/29/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection 8/29/08
Outstanding Inspections
Case Number: T08FR02584
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2008 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Correction Required | Missing or moved ceiling tiles: TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____ Replace missing ceiling tiles. |
08/29/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | Illumination emergency power 1006.3 - . The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate. _____ Emergency exit and emergency egress lights (and their respective battery back-up charging systems) shall be re-wired so that they are on an electrical circuit that is independent from the overhead lights. This circuit shall be equipped with a lock-out type circuit breaker). |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02584
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE |
10/14/2008 | COMPL - REINSPECTION | DGREENLE | Approved | APPROVED |