Case: T08FR02565
Case Details
Entered Date:
08/27/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection 8/26/08
Outstanding Inspections
Case Number: T08FR02565
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | 1011.2 Illumination. Exit signs shall be internally or externally illuminated. _____ Replace batteries in exit light over door to breakroom. _____ Replace batteries in exit light over back door in breakroom. |
08/27/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ repair emergency lighting in Dr's office _____ repair emergency lighting in breakroom |
10/01/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02565
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2008 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy ON FILE AND DISPLAYED |
11/18/2008 | INSP - REINSPECTION | DGREENLE | Approved |