Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/27/2008

Applicant:

PARK MALL LLC

Description:

Full Inspection 8/26/08

Outstanding Inspections

Case Number: T08FR02565
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
08/27/2008 VIOL - MEANS OF EGRESS DGREENLE Violation 1011.2 Illumination. Exit signs shall be internally or externally illuminated. _____ Replace batteries in exit light over door to breakroom. _____ Replace batteries in exit light over back door in breakroom.
08/27/2008 VIOL - MEANS OF EGRESS DGREENLE Violation TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ repair emergency lighting in Dr's office _____ repair emergency lighting in breakroom
10/01/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02565
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/26/2008 INSP - FULL DGREENLE Approved Certificate of Occupancy ON FILE AND DISPLAYED
11/18/2008 INSP - REINSPECTION DGREENLE Approved