Case: T08FR02539
Case Details
Entered Date:
08/27/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection 8/26/08
Outstanding Inspections
Case Number: T08FR02539
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2008 | INSP - FULL | DGREENLE | Correction Required | Certificate of Occupancy: NOT CURRENT - Occupant shall obtain a current C of O. Occupancy Class/Hazard Level have NOT changed. |
08/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels. |
08/27/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet in width. _____ Reduce obstruction to sprinkler flow in cage. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02539
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2008 | COMPL - REINSPECTION | DGREENLE | Approved | All noted hazards mitigated Maintain clearance around electrical panels |