Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/27/2008

Applicant:

PARK MALL LLC

Description:

Full Inspection 8/26/08

Outstanding Inspections

Case Number: T08FR02539
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
08/26/2008 INSP - FULL DGREENLE Correction Required Certificate of Occupancy: NOT CURRENT - Occupant shall obtain a current C of O. Occupancy Class/Hazard Level have NOT changed.
08/27/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels.
08/27/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet in width. _____ Reduce obstruction to sprinkler flow in cage.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02539
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/01/2008 COMPL - REINSPECTION DGREENLE Approved All noted hazards mitigated Maintain clearance around electrical panels