Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/25/2008

Applicant:

CITY OF TUCSON

Description:

Request for Inspector

Outstanding Inspections

Case Number: T08FR02499
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
08/25/2008 INSP - FULL RESSLING Correction Required Email from LD 7, A shift: "Found a 'yard stick' with its gates frozen up and it appears inoperable. It is on outside of complex on the west side and had two 2.5-inch gated valves."
08/25/2008 INSP - FULL TKNAPP Correction Required Found riser with two control valves and FDC at southwest corner of building. Valves appear inoperable. Sprinkler system annual inspection completed on 8/08. Spoke to property manager, faxed report to him.