FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR02497
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
08/25/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.4 NEED A POWER STRIP IN THE NORTH BAY. REMOVE THE MULTI PLUG ADAPTER.
08/25/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE AND TAG SPRINKLER SYSTEM SERVICE AND TAG ALL FIRE EXTINGLUISHERS.
08/25/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 REPAIR THE EXIT SIGN IN FRONT LOBBY REPAIR THE EXIT SIGN IN PARTS ROOM
08/25/2008 VIOL - HAZARDOUS MATERIALS,GEN MWAINWRI Violation 2006 IFC 2703.5.1 IDENTIFY CONTENTS OF THE 2 55 GAL DRUMS
08/25/2008 VIOL - FLAMMABLE LIQUIDS MWAINWRI Violation 2006 IFC 3404.2.7.3 INSTALL A VENT ON YOUR CASTROL OIL TANK

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02497
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/05/2008 INSP - FULL MWAINWRI Approved