Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/20/2008

Applicant:

PRINCE ROAD DESIGN CENTER

Description:

Full Fire Prevention Inspection. Sally Poor 1-800-727-6682

Outstanding Inspections

Case Number: T08FR02475
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/20/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1.Lower the storage height to a minimum of 18 inches below all sprinkler heads.
08/20/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____1.Post a sign on the exterior side of the North door stating "RISER ROOM". ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
08/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1.Remove the tape from the breaker panel located in the Northwest office area.
08/20/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Service, tag and mount all portable fire extinguishers.
08/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1.Post the above wording on the inside of the main entrance/exit door.
08/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____1.The egress door located in the main office shall be free from obstructions.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02475
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/03/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.