Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/20/2008

Applicant:

PRINCE ROAD DESIGN CENTER

Description:

Full Fire Prevention Inspection. Fred Specktor 293-6163

Outstanding Inspections

Case Number: T08FR02468
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
08/20/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____1.Remove all storage from around the sprinkler system riser pipe and control valve.
08/20/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____1.Post a sign on the exterior side of the Northeast door stating "RISER ROOM INSIDE". _____2.Post a sign above the riser room door located in the back office stating "RISER ROOM".
08/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the white extension cord located behind the copy machine.
08/20/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Service and tag the automatic sprinkler system or provide documentation of the current inspection report. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) __ ____________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
08/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1.Post the above wording above the main entrance door.
08/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1.Remove the surface bolt from the northeast egress door.
08/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____1.Remove 1 of the 2 thumb-turn locks from the northeast door.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02468
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/19/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.