Case: T08FR02462
Case Details
Entered Date:
08/20/2008
Applicant:
HIMMELMANN JOHN D & PAMELA A JT/RS
Description:
Complaint
Outstanding Inspections
Case Number: T08FR02462
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2008 | INSP - FULL | RESSLING | Correction Required | Railroad ties have been placed around a hydrant as decoration, but may have rendered it unaccessible. |
| 08/20/2008 | VIOL - FIRE SERVICE FEATURES | NSPRENGE | Violation | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. |
| 08/20/2008 | VIOL - FIRE SERVICE FEATURES | NSPRENGE | Violation | 508.5.5 Clear space around hydrants. A 3-foot (914 mm) clear space shall be maintained around the circumference of fire hydrants except as otherwise required or approved. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02462
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | COMPL - REINSPECTION | NSPRENGE | Approved | The logs have been removed and hydrant is accesible. |