Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/20/2008

Applicant:

PRINCE ROAD DESIGN CENTER

Description:

Full Fire Prevention Inspection. Phone # 408-9919

Outstanding Inspections

Case Number: T08FR02461
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
08/20/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____1.Post a sign on the exterior side of the northwest door stating "RISER ROOM INSIDE". _____2.Post a sign above the riser room door inside the shop stating "RISER ROOM".
08/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1.All electrical wiring below 8 feet in height shall be protected by approved electrical conduit.
08/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the green extension cord located next to the saw in the West workshop. _____2.Remove the extension cords used in the owner's office. NOTE:Replace the extension cord with a fused multi plug adapter.
08/20/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Service and tag all portable fire extinguishers. _____2.Service and tag the automatic sprinkler system or provide documentation of the current inspection.
08/20/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. _____1.Remove the top of the portable spray booth when storing it inside the building. _____2.Additional sprinkler heads shall be installed under the storage shelfing located in the northeast workshop for proper sprinkler system coverage. NOTE:If the shelfing is removed additional sprinkler heads are not required. _____3.The signs being stored near the ceiling shall be separated from each other so the proper sprinkler system coverage will be maintained.
08/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1.Remove the keyed lock and locking hasp from all 3 north side exterior doors. _____2.Remove the lumber from blocking the use of the north exterior door.
08/20/2008 VIOL - WELDING & OTHER HOT WRK JBURGE Correction Required TFC 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. _____1.A poprtable fire extinguisher with a minimum 2-A:20-B:C rating shall be located in the welding and cutting areas. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
08/20/2008 VIOL - HAZARDOUS MATERIALS,GEN JBURGE Correction Required TFC 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. _____1.Properly label all containers to identify the product it contains.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02461
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/03/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.