Case Number: T08FR02373
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Exposed wiring at west wall shall be installed into conduit. Junctions shall be made in junction boxes. |
08/11/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Light fixture at ceiling in storage area shall be secured to ceiling. |
08/11/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 Multiplug adapter used at ceiling light fixture to the south of the walk in cooler shall not be used. |
08/11/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The electrical switch for the light behind the cooler at wine storage area shall be in a junction box. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02373
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/25/2008 | INSP - FULL | TKNAPP | Approved |