Case: T08FR02206
Case Details
Entered Date:
07/31/2008
Applicant:
FGI FINANCING I CORP
Description:
Sprinkler head went off over stove on 7/30 engine 7 responded John N. red tag system, needs follow up, ASC following up today contact Lewis Martinez 275-5453 (The Forume)
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02206
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2008 | INSP - FULL | ALOPEZ | Approved | Sprinkler head went off on call inspector John N, red tag system inspector needs to follow up contact Louis Martinez 275-5453 |
07/31/2008 | INSP - FULL | RSPANGLE | Approved | AN INSPECTION REPORT WAS ISSUED FOR UPGRADING THE SYSYTEM TO A UL 300 EXTINGUISHING SYSTEM. FOLLOW UP WILL BE DONE THROUGH REPORT #T08FR02209. THIS COMPLAINT IS CLOSED. |
07/31/2008 | INSP - FULL | RSPANGLE | Approved | THIS TYPE 1 HOOD HAS REGULAR SPRINKLER HEADS DISCHARGING WATER ON DEEP FAT FRYERS, STOVE AND GRILL AREA. THESE ARE TO REMAIN RED TAGGED UNTIL AN APPROVED LU 300 SYSTEM IS INSTALLED AND APPROVED BY SYSTEM DESIGN. ASL SPECIAL SYSTEMS GROUP WILL BE APPLYING FOR THE PERMIT AND DOING THE INSTALLATION. |