Description:

FULL FIRE INSPECTION.

Outstanding Inspections

Case Number: T08FR02071
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
07/22/2008 INSP - FULL JVINCENT Violation FULL FIRE INSPECTION. GH CHECK LIST USED.
07/22/2008 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Violation TFC 605.1 1) OUTLETS IN MAIN TV ROOM NEED COVER PLATES. OUTLET NEXT TO TV AND OUTLET NEXT TO COUCH.
07/22/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 903.2.7 1) RESIDENTIAL SPRINKLER SYSTEM REQUIRED BY OCT. 22, 2010
07/22/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 907.2.10 1) REPAIR SMOKE DETECTOR IN LAUNDRY ROOM.
07/22/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation TFC 907.3.1.8 1) FIRE ALARM REQUIERED IN NONSPRINKLERED R-4'S. ONE PULL STATION WITH ONE AUDIBLE DEVICE, OK. LOCATED NEAR MAIN EXIT. LOCAL ALARM ONLY.
07/22/2008 VIOL - MEANS OF EGRESS JVINCENT Violation TFC 1011.1 1) EXIT SIGNS REQUIRED OVER BOTH EXITS. CURRENT LIGHTING UNITS WILL SUFFICE FOR EXTERNALLY ILLUMINATED EXIT SIGNS.