Full Fire Inspection Building Rep: Charlie Sommers Phone # 520-770-1797

Outstanding Inspections

Case Number: T08FR02039
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
07/17/2008 INSP - FULL JLONGO Correction Required Full Fire prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
07/17/2008 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code. 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. (OFFICE)
07/17/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ The front main entrance door secondary locking device shall be disabled or replaced to meet code standards. I.E. the lock shall release when twisted from the interior side. _____ The secondary door shall be disabled or replaced to meet code standards. I.E. the lock shall release when twisted from the interior side. Also the double keyed lock shall be removed. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ The two slide bolts shall be removed from the rear egress door to be code compliant
07/17/2008 VIOL - LIQUID PETROLEUM GASES JLONGO Correction Required 3801.1 Scope. Storage, handling and transportation of liquefied petroleum gas (LP-gas) and the installation of LP-gas equipment pertinent to systems for such uses shall comply with this chapter and NFPA 58. Properties of LP-gases shall be determined in accordance with Appendix B of NFPA 58. _____ The propane tank is not allowed and shall be removed from the building. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ____________________ Passed on: ________ (Joseph P. Longo)