Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/17/2008

Applicant:

INDUSTRIAL PLAZA II

Description:

Full Fire Inspection Building Rep: Linda Scott Phone # 623-2346

Outstanding Inspections

Case Number: T08FR02036
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
07/17/2008 INSP - FULL JLONGO Correction Required Full Fire prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
07/17/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code
07/17/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ The front main entrance door secondary locking device shall be disabled or replaced to meet code standards. I.E. the lock shall release when twisted from the interior side. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ The slide bolt shall be removed from the rear egress door and/or replaced with a approved locking device. the door shall comply with the code 1008.1.8.5 ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ____________________ Passed on: ________ (Joseph P. Longo)