Full Fire Prevention Inspection. Crystal Keck 882-0707

Outstanding Inspections

Case Number: T08FR02030
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
07/17/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove all storage from obstructing the electrical service equipment located in the back room.
07/17/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following method: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. _____1. Properly secure the Helium cylinder located in the back room to prevent the cylinder from falling. __ _____________________________________________ (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02030
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/08/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.