Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/17/2008

Applicant:

WEST MAIN GATE CENTER LLC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR02000
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
07/17/2008 VIOL - ADMINISTRATION MWAINWRI Violation 2006 IFC 101.1 NEED TO SEE PLANS AND PERMIT FOR THE NEW PIZZA ROOM
07/17/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.1 INSTALL MISSING ELECTRICAL OUTLET PLATE COVER UPSTAIRS AT THE BAR
07/17/2008 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.5 REMOVE EXTENSION CORD IN BOX OFFICE
07/17/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE FIRE EXTINGUISHER AT CABANA AREA SERVICE FIRE EXTINGUISHER UNDER STAIRS
07/17/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.6.1 REPLACE MISSING FILTER UNDER HOOD
07/17/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.6.3 CLEAN BOTH HOODS, DUCT TO ROOF
07/17/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 REPAIR THE EMERGENCY LIGHTS IN THE FOLLOWING AREAS IN THE SERVER HALLWAY BY MENS/WOMENS BATHROOM DOWN STAIRS 1ST LANDING IN INSIDE STAIR CASE IN CABANA AREA AT BENCH SEATING UPSTAIRS IN KITCHEN IN PIZZA ROOM

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02000
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/18/2009 INSP - FULL MWAINWRI Approved