Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/17/2008

Applicant:

MASSAPEQUA ASSOCIATES LLC

Description:

Full Fire Prevention Inspection. Jeremy Noles 624-7667

Outstanding Inspections

Case Number: T08FR01972
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
07/17/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Open spaces in the electrical panel located in the warehouse area shall be covered with electrical blanks.
07/17/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Remove the surface bolts from the exit door located in the warehouse area.
07/17/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair the emergency lighting unit located on the Northeast wall in the sales area. {Replace the light bulb.}
07/17/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove all storage from blocking the Northwest exit door. _____2. Remove all storage from blocking the exit door located in the warehouse.
07/17/2008 VIOL - HAZARDOUS MATERIALS,GEN JBURGE Correction Required TFC 2703.11 GroupMstorage and display and Group S storage. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored and displayed within a single control area of a Group Moccupancy, or an outdoor control area, or stored in a single control area of a Group S occupancy, is allowed to exceed the maximum allowable quantity per control area indicated in Section 2703.1 when in accordance with Sections 2703.11.1 through 2703.11.3.10. _____1. Comply with with the above noted Fire Code requirements. {See the attached pool chemical storage requirements for M and S occupancies.} ________________________________________________ (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01972
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/14/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.