Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

07/16/2008

Applicant:

FRIS CHKN LLC

Description:

Complaint

Outstanding Inspections

Case Number: T08FR01956
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
07/23/2008 INSP - FULL EGRIFFIN Violation On 8-6-08, a fire prevention inspection was conducted at Church's Fried Chicken at 7090 East Golf Links in Tucson, Arizona. The following Tucson Fire Code Violation(s) was noted: Currently kitchen hood extinguishing system is not in compliance with fire code requirements. This is indicated by the semi annual hood system report and a non-compliance tag on manual activation device. The fire code requires: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. Please ensure current certificate or tags are affixed to manual activation devices by 8-6-08