Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

07/16/2008

Applicant:

GS PROPERTY INVESTMENTS LLC

Description:

Complaint

Outstanding Inspections

Case Number: T08FR01952
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
08/21/2008 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Correction Required Inspected system on 8/19. Appliance sticks out slightly, not completely covered by suppression system. RI in 2 weeks to correct coverage. 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. -ensure total and proper coverage of appliances under hood.
08/27/2008 INSP - FULL BCORRALE Continued Spoke with Rosa, a rep from Viva burrito, they will bid out the job to extend hood system immediately. Will check on progress during re-inspection, approx. 9/10.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01952
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/14/2009 INSP - REINSPECTION JLOYA Approved Appliances re-arranged in order to meet code.