Case: T08FR01887
Case Details
Entered Date:
07/15/2008
Applicant:
CONCORD VENTURES LLC
Description:
SPRINKLER INSPECTION
Outstanding Inspections
Case Number: T08FR01887
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2008 | INSP - FULL | EDESCHAI | Correction Required | 901.6 mAINTENANCE OF FIRE PROTECTION SYSTEMS 1) PROVIDE PROTECTIVE CAPS FOR THE FIRE DEPT. CONNECTION 2) REMOVE THE BIRD NEST FROM THE ALARM BELL AT THE SPRAY BOOTH 3) tHE SPRINKLER RISER SHALL BE KEPT FREE OF ALL STORAGE 4) pROVIDE THE 5 YEAR INSPECTION OF THE CHECK VALVE 5) PROVIDE THE CORRECT NUMBER OF SPARE HEADS TO THE HEAD BOX |