Outstanding Inspections

Case Number: T08FR01884
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
07/14/2008 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 Storage shall not be located in NW electrical room.
07/14/2008 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.3.1 Combustible materials shall not be stored or displayed under non-sprinklered eaves on east side of building.
07/14/2008 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 508.5.4 Storage shall not be allowed to block access to sprinkler control valve.
07/14/2008 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Fire extinguisher.
07/14/2008 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6.2 Sprinkler inspection records shall be provided.
07/14/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 Emergency light at NW hallway.
07/14/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 Emergency light in stockroom.
07/14/2008 VIOL - HIGH PILED COMBUSTIBLES TKNAPP Correction Required 2305.4 Aisles in stockroom shall be maintained.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01884
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/12/2008 INSP - FULL TKNAPP Approved