Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T08FR01857
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
07/10/2008 INSP - FULL JNAGORE Violation 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. 3 Inch lettering with contrasting colors that reads, Fire Department Riser Room. At every riser room door on site.
07/10/2008 INSP - FULL JNAGORE Violation 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1. 901.6.2 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. 901.7 Systems out of service. Where a required fire protection system is out of service, the fire department and the fire codeofficial shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. Where utilized, fire watches shall be provided with at least one approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires. This system and all Fire Dept. systems need to be checked and working properly. Yearly test are required for all Fire Dept equipment.
07/10/2008 INSP - FULL JNAGORE Violation KEY BOX. A secure, tamperproof device with a lock operable only by a fire department master key, and containing building entry keys and other keys that may be required for access in an emergency. Lock Boxes are available at Fire Prevention Center. 797 E. Ajo Way. 791-4502 for more info.